Mitsubishi 1900 kVA

Værktøjkasse

Har du brug for svar og rådgivning?

Quick Data view

Output Power

Standby Power (ESP)

kVA

1908

kW

1526

Prime Power (PRP)

kVA

1750

kW

1400

Size

W x L x H (mm)

Weight (kg)

Fuel Tank (lt)

Noise dB(A) @ 7m

Canopied

2470x9145x3150

18493

2350

96

Open Skid

2250x5210x2750

12413

3500

N/A

Manufacturer

MITSUBISHI

Model

S16R-PTA

Cylinder Configuration

V TYPE

No of Cylinders

16

Displacement

lt

65,37

Bore

mm

170

Stroke

mm

180

Compression Ratio

14:01

Aspiration

TURBOCHARGE-AFTERCOOLER

Governor Type

ELECTRONIC

Cooling System

WATER

Coolant Capacity

lt

345

Lubrication Oil Capacity

lt

230

Electrical System

VDC

24

Speed / Frequency 50 Hz

rpm

1500 rpm / 50 Hz

Engine Gross Power (Standby 50 Hz)

kW

1620

Fuel Consumption %110 ESP 50 Hz

lt/h

388

Fuel Consumption %100 PRP 50 Hz

lt/h

353

Fuel Consumption %75 PRP 50 Hz

lt/h

266

Fuel Consumption %50 PRP 50 Hz

lt/h

188

Exhaust Outlet Temperature 50 Hz

°C

539

Exhaust Gas Flow 50 Hz

m3/min

339

Combustion Air Flow 50 Hz

m3/min

128

Cooling Air Flow 50 Hz

m3/min

1950

Manufacturer

LEROY-SOMER

Model

LSA 52.3 S5

No of Phases

3

Power Factor

0,8

No of Bearings

SINGLE

No of Poles

4

No of Leads

6

Voltage Regulation (Steady State)

± %0,5

Insulation Class

H

Degree of Protection

IP 23

Excitation System

AVR (Automatic Voltage Regulator); Brushless

Connection Type

STAR

Total Harmonic Content (No Load)

< %4

Frequency

Hz

50

Voltage Output 50 Hz

VAC

230 / 400

Rated Power (Standby) 400_50 Hz

kVA

2046

Efficiency (4/4_400 V_50 Hz)

%

95,8

Standard Equipments

Standard Equipments
Engine
In Teksan generator sets, leading engine brands that have state of the art technology and have compliance with ISO 8528, ISO 3046, BS 5514, DIN 6271 standarts, are being used. These engines with low fuel consumption, provide accurate speed setting and order, mount to the fuel pump, also have mechanic or electronic type governors.

Alternator
In products Teksan produced, leading alternator brands of the world that have state of the art technology, high quality, productivity and durability, are being used. All alternators, which pass necessary test process and found appropriate according to EC 60034-1; CEI EN 60034-1; BS 4999-5000; VDE 0530, NF 51- 100,111; OVE M-10, NEMA MG 1.22. standarts, have bearing system that does not need maintenance, with electronic type voltage regulator providing voltage setting.

Control Panel
Standard control panel, that is used in Teksan generator sets, ensures comfortable and safe usage. All measured and statistical parameters, operating modes, notice and alarms and condition of generator, are monitored easily from the control panel. On the front of the panel’s metal body has electronic control module and the emergency stop button and the panel’s metal body is made of steel sheet and is painted with electrostatic powder paint.

Teksan offers panel design and solutions that comply with special requirements of customers as well as quality standard panels.

Chassis and Fuel Tank
Chassis is manufactured from steel that has features and durability for carrying burden of generator set. Thanks to its rigid structural design and anti-vibration mounts, it reduces vibration level to minimum. All chassis contain lifting lugs. Apart from chassises that are produce by Teksan, special solutions that design in accordance with customer desires, make transportation and positioning easier.

In less than 1600 kVA power generator sets, fuel tank is produced integratedly to the chassis. In more than 1600 kVA power generator sets, rectangular type fuel tank is provided with generator set seperately. In all types of fuel tank have its level and indicator.

Cooling System
System, that consists of quality industrial – type radiator, expansion tank and cooler fan, keeps the temprature of generator set’s equipments constant at a proper level.

Canopy Features
TEKSAN Standard Canopies’ default features are as follows;

Compatible with 2000/14/EC directives, certified noise emission level,
2 or 4 points transport possibility according to cabin size,
Hidden exhaust inside the canopy,
Emergency stop button located on the canopy,
Improved air suction channel to ensure homogenous cooling in the canopy,
Radiator air outlet and exhaust with designed towards above,
Lid on cab that provides to be filled up water and antifreeze easily to the radiator,
Amplified paint system against corrosion and rust,
Improved performance in terms of sound insulation,
Demounted parts that make transportation and maintenance easier,
As well as the standard range of canopies, TEKSAN can also design tailormade canopies with specific sound level or size upon customer requests.

Optional Equipments
Some Optional Equipments that Teksan provides with Generator Sets;

Medium voltage alternator,
Remote radiator applications,
Automatic fuel filling system,
Fuel tank, oil pan, dashboard, alternator, coil heaters,
Alternator with double AVR and PMG,
Synchronization systems,
The generator output breaker,
Grid-generator transfer switches,
Accordance with the specific volume of demand-insulated cabins,
Seismic solutions,
Trailer,
Remote monitoring,
DSE Control panel,
DEIF Control panel.

Control Panel Features-TJ 509-T
The TJ-509T is a next generation genset control unit combining multi-functionality and wide communication possibilities together with a reliable and low cost design.
The unit complies and mostly exceeds world’s tightest safety, EMC, vibration and environmental standards for the industrial category.
Software features are complete with easy firmware upgrade process through USB port. The Windows based PC software allows monitoring and programming through USB, RS-485, Ethernet and GPRS.
The PC and server based Rainbow Scada software allows monitoring and control of an unlimited number of gensets from a single central location.

Functions
AMF unit with uninterrupted transfer
ATS unit with uninterrupted transfer
Remote start controller
Manual start controller
Engine controller
Remote display & control unit
Waveform display of V & I
Harmonic analysis of V & I
CTs at genset or load side

Communications
SM-GPRS
Web monitoring
Web programming
GSM-SMS
e-mail
USB Device
RS-232
J1939-CANBUS

Topologies

2 phase 3 wires, L1-L2
2 phase 3 wires, L1-L3
3 phase 3 wires, 3 CTs
3 phase 3 wires, 2 CTs (L1-L2)
3 phase 3 wires, 2 CTs (L1-L3)
3 phase 4 wires, star
3 phase 4 wires, delta
1 phase 2 wires

Hent Komplet Datablad