Mitsubishi 1375 kVA
Quick Data view
Output Power
Standby Power (ESP)
kVA
1375
1100
Prime Power (PRP)
kVA
1250
kW
kW
Size
W x L x H (mm)
Weight (kg)
Fuel Tank (lt)
Noise dB(A) @ 7m
Canopied
2470x6080x2930
13093
1540
92
Open Skid
2050x4500x2390
9403
1540
N/A
Manufacturer
MITSUBISHI
Model
S12R-PTA
Cylinder Configuration
V TYPE
No of Cylinders
12
Displacement
lt
49,03
Bore
mm
170
Stroke
mm
180
Compression Ratio
14:01
Aspiration
TURBOCHARGE-AFTERCOOLER
Governor Type
ELECTRONIC
Cooling System
WATER
Coolant Capacity
lt
300
Lubrication Oil Capacity
lt
180
Electrical System
VDC
24
Speed / Frequency 50 Hz
rpm
1500 rpm / 50 Hz
Engine Gross Power (Standby 50 Hz)
kW
1220
Fuel Consumption %110 ESP 50 Hz
lt/h
300
Fuel Consumption %100 PRP 50 Hz
lt/h
271
Fuel Consumption %75 PRP 50 Hz
lt/h
208
Fuel Consumption %50 PRP 50 Hz
lt/h
151
Exhaust Outlet Temperature 50 Hz
°C
492
Exhaust Gas Flow 50 Hz
m3/min
258
Combustion Air Flow 50 Hz
m3/min
98
Cooling Air Flow 50 Hz
m3/min
1800
Manufacturer
LEROY-SOMER
Model
LSA 50.2M6
No of Phases
3
Power Factor
0,8
No of Bearings
SINGLE
No of Poles
4
No of Leads
6
Voltage Regulation (Steady State)
± %0,5
Insulation Class
H
Degree of Protection
IP 23
Excitation System
AVR (Automatic Voltage Regulator), Brushless
Connection Type
STAR
Total Harmonic Content (No Load)
< %3,5
Frequency
Hz
50 / 60
Voltage Output 50 Hz
VAC
230 / 400
Rated Power (Standby) 400_50 Hz
kVA
1375
Efficiency (4/4_400 V_50 Hz)
%
94,9
Standard Equipments
Standard Equipments
Engine
In Teksan generator sets, leading engine brands that have state of the art technology and have compliance with ISO 8528, ISO 3046, BS 5514, DIN 6271 standarts, are being used. These engines with low fuel consumption, provide accurate speed setting and order, mount to the fuel pump, also have mechanic or electronic type governors.
Alternator
In products Teksan produced, leading alternator brands of the world that have state of the art technology, high quality, productivity and durability, are being used. All alternators, which pass necessary test process and found appropriate according to EC 60034-1; CEI EN 60034-1; BS 4999-5000; VDE 0530, NF 51- 100,111; OVE M-10, NEMA MG 1.22. standarts, have bearing system that does not need maintenance, with electronic type voltage regulator providing voltage setting.
Control Panel
Standard control panel, that is used in Teksan generator sets, ensures comfortable and safe usage. All measured and statistical parameters, operating modes, notice and alarms and condition of generator, are monitored easily from the control panel. On the front of the panel’s metal body has electronic control module and the emergency stop button and the panel’s metal body is made of steel sheet and is painted with electrostatic powder paint.
Teksan offers panel design and solutions that comply with special requirements of customers as well as quality standard panels.
Chassis and Fuel Tank
Chassis is manufactured from steel that has features and durability for carrying burden of generator set. Thanks to its rigid structural design and anti-vibration mounts, it reduces vibration level to minimum. All chassis contain lifting lugs. Apart from chassises that are produce by Teksan, special solutions that design in accordance with customer desires, make transportation and positioning easier.
In less than 1600 kVA power generator sets, fuel tank is produced integratedly to the chassis. In more than 1600 kVA power generator sets, rectangular type fuel tank is provided with generator set seperately. In all types of fuel tank have its level and indicator.
Cooling System
System, that consists of quality industrial – type radiator, expansion tank and cooler fan, keeps the temprature of generator set’s equipments constant at a proper level.
Optional Equipments
Some Optional Equipments that Teksan provides with Generator Sets;
Medium voltage alternator,
Remote radiator applications,
Automatic fuel filling system,
Fuel tank, oil pan, dashboard, alternator, coil heaters,
Alternator with double AVR and PMG,
Synchronization systems,
The generator output breaker,
Grid-generator transfer switches,
Accordance with the specific volume of demand-insulated cabins,
Seismic solutions,
Trailer,
Remote monitoring.
Canopy Features
TEKSAN Standard Canopies’ default features are as follows;
Compatible with 2000/14/EC directives, certified noise emission level,
2 or 4 points transport possibility according to cabin size,
Hidden exhaust inside the canopy,
Emergency stop button located on the canopy,
Improved air suction channel to ensure homogenous cooling in the canopy,
Radiator air outlet and exhaust with designed towards above,
Lid on cab that provides to be filled up water and antifreeze easily to the radiator,
Amplified paint system against corrosion and rust,
Improved performance in terms of sound insulation,
Demounted parts that make transportation and maintenance easier,
As well as the standard range of canopies, TEKSAN can also design tailormade canopies with specific sound level or size upon customer requests.
Control Panel Features-TJ 509-T
The TJ-509T is a next generation genset control unit combining multi-functionality and wide communication possibilities together with a reliable and low cost design.
The unit complies and mostly exceeds world’s tightest safety, EMC, vibration and environmental standards for the industrial category.
Software features are complete with easy firmware upgrade process through USB port. The Windows based PC software allows monitoring and programming through USB, RS-485, Ethernet and GPRS.
The PC and server based Rainbow Scada software allows monitoring and control of an unlimited number of gensets from a single central location.
Functions
AMF unit with uninterrupted transfer
ATS unit with uninterrupted transfer
Remote start controller
Manual start controller
Engine controller
Remote display & control unit
Waveform display of V & I
Harmonic analysis of V & I
CTs at genset or load side
Communications
SM-GPRS
Web monitoring
Web programming
GSM-SMS
e-mail
USB Device
RS-232
J1939-CANBUS
Topologies
2 phase 3 wires, L1-L2
2 phase 3 wires, L1-L3
3 phase 3 wires, 3 CTs
3 phase 3 wires, 2 CTs (L1-L2)
3 phase 3 wires, 2 CTs (L1-L3)
3 phase 4 wires, star
3 phase 4 wires, delta
1 phase 2 wires
Værktøjkasse